Compressed air and compressor room monitoring

Compressed air is the utility a plant notices only when the pressure falls and a line stops. A controller in the compressor room reports receiver pressure, motor load and discharge temperature, and the record shows what nobody sees on a walk-round: the compressor running all weekend to feed leaks.

A maintenance fitter in ear defenders checks a joint on blue compressed air pipework on a factory floor

What goes wrong without it

Pressure drops during production

Demand outgrows supply, or a compressor trips, and the first alarm is a machine stopping on the line.

Leaks run the compressor

A system that loads all weekend with the plant closed is feeding leaks, and nothing on a weekday shows it.

Overheating ends in a trip

A blocked cooler or a hot room raises discharge temperature for days before the compressor shuts itself down.

What gets read in a compressor room

SignalHow it is readWhat it tells you
Receiver and line pressureAnalogue pressure transducersWhether supply keeps up with demand
Motor currentClamp-on current sensor over RS485Loaded, unloaded and stopped time
Discharge temperaturePT1000 probeOverheating before a trip
Room temperature1-Wire probeA compressor room too hot to run in
Compressor controllerRS485 Modbus RTU, from its register mapHours, service counters and alarm codes

Four ports on one Genesis controller, and RS485 devices share a bus, so most sites need one unit.

From a reading to the person on call

Thresholds per point

Minimum and maximum on each sensor, with alerts to the people on the list. Acknowledgement is recorded against the alarm, so a handover shows what was already seen.

Nothing lost when the link drops

Readings are stored on the controller with their time and sent in order when coverage returns, so the record has no gap where the incident was.

A history you can hand over

Full-resolution history, exported to Excel for a report, an insurer or a contractor, or pulled into your own system through the REST API.

Contractors see what they maintain

A device can be shared with a service company without sharing a login, and they see nothing else on your account.

Sensors and pages for this application

Frequently asked questions

How does it show leaks?

Through load out of hours. With production stopped, the time the compressor spends loaded is almost entirely leakage, and the record shows it night after night.

Can it read several compressors?

Yes. Current sensors and controllers share the RS485 bus, and each is filed against its own compressor.

Does it need a network or a power supply at the site?

Neither. The controller connects over 4G-LTE and runs on its rechargeable battery, with solar or a 6 to 32 V DC supply where readings need to be frequent.

Can we keep the instruments already installed?

Usually, yes. Over fifty sensor types are supported today and more are added on request, including RS485 Modbus instruments from their register map.

Tell us about the site

What needs watching, which instruments are already there, and whether the site has power and coverage. We come back with what a Genesis would read and what the installation involves.