CO2 detection for beverage cellars and dispense rooms

A beverage cellar stores CO2 in cylinders or a bulk tank in a small room below ground. A leak sinks and fills the room from the floor up, without a smell. A detector low on the wall sounds an alarm at the door before anyone walks in, and reports the reading over cellular.

Why CO2 is the hazard here

Heavier than air

CO2 sinks and collects in cellars and pits, where it stays without ventilation.

No warning of its own

It is colourless and odourless, and at high concentration it is toxic as well as displacing air.

Cylinder changes

The moment of connecting and disconnecting cylinders is when releases happen.

How the detection point is specified

Target gasCarbon dioxide (CO2)
Selectable ranges0-1000 / 2000 / 5000 ppm / 0-20 %VOL
Mounting heightLow, 0.3 to 0.6 m above floor level: the gas is heavier than air
Where the detectors goLow on the wall near the cylinders or bulk tank; near the cellar entrance; in the dispense room beside the regulators
OutputsTwo alarm relays, 4-20 mA and RS485 Modbus RTU, all at once
ReportingRS485 into a Genesis controller, then over cellular to alerts and a record

What happens when it alarms

The room acts first

The detector relays switch the fan, close the valve or sound the beacon locally, with no network involved.

Then people are told

The same reading goes over cellular to the people on the alert list, wherever they are, with acknowledgement recorded.

And the event is kept

Concentration, time and duration are kept on a record that exports to Excel, for the incident review and the next inspection.

Detectors and related pages

Frequently asked questions

Which range suits a cellar?

The ppm ranges cover ventilation and air quality; the 0 to 20 %VOL range covers leak detection around bulk CO2 storage, where concentration can climb far beyond the ppm scale.

What are the workplace exposure limits for carbon dioxide?

The NIOSH Pocket Guide lists a recommended exposure limit of TWA 5000 ppm (9000 mg/m³) ST 30,000 ppm (54,000 mg/m³), an OSHA permissible exposure limit of TWA 5000 ppm (9000 mg/m³) and an IDLH of 40,000 ppm. These are United States values; set alarm points against the rules that apply at your site.