Chlorine detection for water treatment and chlorination rooms

Water treatment stores chlorine in cylinders and drums in a room most people only enter to change them. Chlorine is heavier than air and settles to the floor. Detectors low on the wall trip the local alarm and the scrubber or fan on their own relays and report the reading over cellular.

Why chlorine is the hazard here

Toxic at low concentration

Chlorine irritates the airways at a few ppm and is dangerous well before it is visible.

Heavier than air

A release flows to the floor and into drains, pits and low rooms.

Unattended rooms

Chlorination rooms and cylinder stores are visited occasionally, so a leak can run for hours.

How the detection point is specified

Target gasChlorine (Cl2)
Selectable ranges0-10 / 20 / 50 / 100 / 200 ppm
Mounting heightLow, 0.3 to 0.6 m above floor level: the gas is heavier than air
Where the detectors goLow on the wall near cylinders and drums; at the chlorinator and the injection point; at the room entrance, outside the door
OutputsTwo alarm relays, 4-20 mA and RS485 Modbus RTU, all at once
ReportingRS485 into a Genesis controller, then over cellular to alerts and a record

What happens when it alarms

The room acts first

The detector relays switch the fan, close the valve or sound the beacon locally, with no network involved.

Then people are told

The same reading goes over cellular to the people on the alert list, wherever they are, with acknowledgement recorded.

And the event is kept

Concentration, time and duration are kept on a record that exports to Excel, for the incident review and the next inspection.

Detectors and related pages

Frequently asked questions

Which range suits a chlorination room?

The 0 to 10 ppm range is the usual choice for chlorination rooms and cylinder stores. The higher ranges are for process areas where a release would be large.

What are the workplace exposure limits for chlorine?

The NIOSH Pocket Guide lists a recommended exposure limit of C 0.5 ppm (1.45 mg/m³) [15-minute], an OSHA permissible exposure limit of C 1 ppm (3 mg/m³) and an IDLH of 10 ppm. These are United States values; set alarm points against the rules that apply at your site.