Ammonia detection for refrigeration plant rooms

Ammonia is an efficient refrigerant and a toxic gas, and a machinery room is where a release starts. Fixed detectors high in the room switch the ventilation on their own relays and send the reading over cellular, so a small leak is found while it is still small.

Why ammonia is the hazard here

A large charge in one room

Industrial refrigeration holds its ammonia in the compressors, vessels and valves of one machinery room.

Lighter than air

A release rises and collects under the roof, so detectors at floor level miss it.

It reaches the people next door

From the machinery room a leak can travel to the cold stores and production areas around it.

How the detection point is specified

Target gasAmmonia (NH3)
Selectable ranges0-50 / 100 / 200 / 500 / 1000 ppm
Mounting heightHigh, 0.3 to 0.6 m below the ceiling: the gas is lighter than air
Where the detectors goAbove compressors and valve stations; high in the machinery room; cold stores and production areas next to the plant
OutputsTwo alarm relays, 4-20 mA and RS485 Modbus RTU, all at once
ReportingRS485 into a Genesis controller, then over cellular to alerts and a record

What happens when it alarms

The room acts first

The detector relays switch the fan, close the valve or sound the beacon locally, with no network involved.

Then people are told

The same reading goes over cellular to the people on the alert list, wherever they are, with acknowledgement recorded.

And the event is kept

Concentration, time and duration are kept on a record that exports to Excel, for the incident review and the next inspection.

Detectors and related pages

Frequently asked questions

What range suits a machinery room?

The 500 and 1000 ppm ranges suit a machinery room, where the alarm starts ventilation and a shutdown. The low ranges suit the occupied areas around it.

What are the workplace exposure limits for ammonia?

The NIOSH Pocket Guide lists a recommended exposure limit of TWA 25 ppm (18 mg/m³) ST 35 ppm (27 mg/m³), an OSHA permissible exposure limit of TWA 50 ppm (35 mg/m³) and an IDLH of 300 ppm. These are United States values; set alarm points against the rules that apply at your site.