4-20 mA scaling calculator

Enter the range the transmitter is set to, then a current to get the value, or a value to get the current it should produce. Useful for commissioning a loop and for checking what a reading should be.

How 4-20 mA scaling works

A straight line between two points

The transmitter maps the bottom of its range to 4 mA and the top to 20 mA. In between it is linear: value = low + (mA - 4) / 16 × (high - low). Sixteen milliamps of span carry the whole range.

Why 4 and not 0

A live zero separates a real minimum reading (4 mA) from a broken wire or a dead transmitter (0 mA). It also leaves the transmitter enough current to power itself on a two-wire loop.

Outside the span

Many transmitters signal a fault by driving the loop below about 3.6 mA or above about 21 mA. A reading outside 4 to 20 mA is worth treating as a fault rather than scaling it into a value.

Frequently asked questions

What does 12 mA mean?

Exactly half of the span. On a 0 to 10 bar transmitter it is 5 bar; on a -50 to 150 °C transmitter it is 50 °C.

How do I read 4-20 mA with a voltage input?

Through a precision resistor: 250 Ω turns 4-20 mA into 1-5 V. Scale the voltage the same way, with 1 V as the bottom of the range and 5 V as the top.

Can the range be negative or reversed?

Yes. Enter the value at 4 mA as the low end and the value at 20 mA as the high end, whatever their signs or order. The calculator follows the line between them.