Ethylene oxide detection for sterilisation areas

Ethylene oxide sterilises what heat would damage, and it is toxic, flammable and a carcinogen with little smell at hazardous levels. Fixed detectors around the sterilisers, aeration rooms and cylinder store alarm locally and keep a record of every excursion, sent over cellular.

Why ethylene oxide is the hazard here

Exposure limits are very low

It is treated as an occupational carcinogen, so limits sit near the bottom of the detector range.

Off-gassing continues

Sterilised goods release it in the aeration room and in storage after the cycle ends.

Little smell at harmful levels

Nobody can rely on noticing it.

How the detection point is specified

Target gasEthylene oxide (C2H4O)
Selectable ranges0-50 / 100 / 200 / 500 / 1000 ppm
Mounting heightLow, 0.3 to 0.6 m above floor level: the gas is heavier than air
Where the detectors goAt steriliser doors and unloading areas; in aeration rooms; at the cylinder store and the gas supply
OutputsTwo alarm relays, 4-20 mA and RS485 Modbus RTU, all at once
ReportingRS485 into a Genesis controller, then over cellular to alerts and a record

What happens when it alarms

The room acts first

The detector relays switch the fan, close the valve or sound the beacon locally, with no network involved.

Then people are told

The same reading goes over cellular to the people on the alert list, wherever they are, with acknowledgement recorded.

And the event is kept

Concentration, time and duration are kept on a record that exports to Excel, for the incident review and the next inspection.

Detectors and related pages

Frequently asked questions

Which range suits a sterilisation area?

The lowest range that still covers the highest concentration expected, chosen with the exposure limits that apply at the site.

What are the workplace exposure limits for ethylene oxide?

The NIOSH Pocket Guide lists a recommended exposure limit of Ca TWA <0.1 ppm (0.18 mg/m³) C 5 ppm (9 mg/m³) [10-min/day], an OSHA permissible exposure limit of [1910.1047] TWA 1 ppm 5 ppm [15-minute Excursion] and an IDLH of Ca [800 ppm]. These are United States values; set alarm points against the rules that apply at your site.